"Buy with Confidence" from BPMA Members

Avoiding Cavitation

If the available system inlet pressure, also termed static pressure, falls bellow the required pump inlet pressure, suitable measures must be taken to achieve at least an equilibrium such as:

  • Increasing the available static pressure at the pump location (positioning the pump at a lower altitude, i.e. from a roof top plant room into the basement to benefit from the increased static head from the higher water column. The pump performance remains unchanged).
  • Lowering the fluid temperature (reducing the vapour pressure pD).
  • Changing the pump characteristics (reducing the driven speed and / or different pump design with a lower pump NPSHr )

Related Topics


Back to Resources